RFP NO |
|
MSU – COOLEY LAB RENOVATION
RFP’S DESCRIPTION/TITLE |
APPROVED
– C/O # |
WORK COMPLETED OR SCHEDULE DATE |
|
|
|
|
|
|
Provide Tackboards |
Change
Order 12 |
May 2013 |
|
|
Install Door between Rm 029 and 005E |
Change Order 12 |
May 2013 |
|
|
Add Gutter & Downspout @ North
Entry Area |
Change Order 12 |
April 2013 |
|
|
Additional snow guards at North
Roof |
Change Order 12 |
March 2013 |
|
|
Revise condensate piping @ EQ4
& Autoclaves |
Change Order 12 |
March 2013 |
|
|
Meters for Steam Generators SG-1
and Autclaves steam gen. |
Change Order 12 |
February 2013 |
|
|
Solenoids @ EQ4 Steam Generators |
Change Order 12 |
February 2103 |
|
|
Additional Shelving in Room 315A |
Change Order 12 |
February 2013 |
|
|
Intermediate shelf at Custom
Tables (3) |
Change Order 12 |
February 2013 |
|
|
Additional Specialty Signage |
Change Order 12 |
February 2013 |
|
|
Trash receptacles |
Change Order 12 |
February 2013 |
|
|
BACnet Interface for Heat Pump HP-1 |
Change Order 12 |
February 2013 |
|
|
Door Handle Replacement for
Incubator |
Change Order 12 |
February 2013 |
|
|
Tubing for Incubators (4) @ four
locations |
Change Order 12 |
February 2013 |
|
|
Revise Electrical Power at Laser
Tables |
Change Order 12 |
February 2013 |
|
|
Provide MED Table for Rm 114 |
Change Order 12 |
February 2013 |
|
|
Provide Blackout Curtains 1st
3rd and 4th floors |
Change Order 12 |
February 2013 |
|
|
Painting Extras |
Change Order 12 |
February 2013 |
|
|
Place LAC-1 Lab Air Compressor on Emergency
Power |
Change Order 12 |
January 2013 |
|
|
Fire Sprinkler Bracing @ Penthouse |
Change Order 12 |
January 2013 |
|
|
Autoclave storage shelving |
Change Order 12 |
January 2013 |
|
|
New Under Shelving Lighting |
Change Order 12 |
January 2013 |
|
|
New Lighting @ Lab Sinks |
Change Order 11 |
January 2013 |
|
|
Revisions to Room 228A – Lab
Air/Black-out Curtains |
Change Order 11 |
February 2013 |
|
|
Add 208v receptacle in Room 430 |
Change Order 10 |
January 2013 |
|
|
Relocate AHU Light Switch |
Change Order 10 |
January 2013 |
|
|
Laser Lab Cord Ends |
Change Order 10 |
January 2013 |
|
|
Phase 3 Post Modifications |
Change Order 10 |
February 2013 |
|
|
Provide Relief on Chilled Water
Return |
Change Order #9 |
November 2012 |
|
|
Provide Chilled Water Bypass &
Control Valving |
Change Order #9 |
November 2012 |
|
|
Provide Stainless Steel Shelving @
ARC Corridor Closet |
Change Order #10 |
November 2012 |
|
|
West Entry Canopy Revisions |
Change Order #9 |
October 2012 |
|
|
Revisions to Autoclave Rm 028 |
Change Order #9 |
October 2012 |
|
|
POST Modifications |
Change Order #9 |
November 2012 |
|
|
Compressed Air to Laser Tables (5
locations) |
Change Order #9 |
October 2012 |
|
|
Elevator GFCI Light and Light
Switch |
Change Order #9 |
October 2012 |
|
|
HWS/HWR lines to Cabinet Heater in
Lewis Entry Vestibule |
Change Order #9 |
October 2012 |
|
|
Door Changes 006B 000 and 001 |
Change Order #9 |
October 2012 |
|
|
Provide Landscaping &
Irrigation North of Taylor Hall |
Change Order #9 |
September 2012 |
|
|
Remove & Replace Mirrors &
Sinks (9) Locations |
Change Order #9 |
September 2012 |
|
|
Provide Seating per the attached
schedule |
Change Order #9 |
September 2012 |
|
|
Provide Water Softener & Hot
Water Control Valve EQ5-6 & 7 |
Change Order #9 |
September 2012 |
|
|
Provide Bypass Loop for Water
Meter |
Change Order #9 |
September 2012 |
|
|
Provide Ladder & Guardrail @
Abandoned Elevator Pit |
Change Order #8 |
September 2012 |
|
|
Add Bypass Loop @ ARC condensate
meter – revise PC routing |
Change Order #8 |
September 2012 |
|
|
Replace Plumbing Fixtures @ Rm 129 |
Change Order #8 |
September 2012 |
|
|
(3 Laser Tables & Accessories |
Change Order #7 |
October 2012 |
|
|
Spring Mounts @ Penthouse on Pipe
Risers |
Change Order #8 |
August 2012 |
|
|
Mechanical Louver Change L5 &
L6 |
Change Order #8 |
August 2012 |
|
|
Remove Steel Column @ Door 102D |
Change Order #8 |
August 2012 |
|
|
Provide AED |
Change Order #8 |
August 2012 |
|
|
Lab 011 Casework Revisions & T-Stat
relocation |
Change Order #8 |
August 2012 |
|
|
Delete Site Lighting |
Change Order #7 |
July 2012 |
|
|
Revise HVAC Access Doors |
Change Order #7 |
July 2012 |
|
|
Delete Bypass Valving
at HWC-1 & HWC-2 |
Change Order #7 |
July 2012 |
|
|
Add Chemical Bypass Feeders |
Change Order #7 |
July 2012 |
|
|
Revise Shelving – add finished
edging |
Change Order #7 |
July 2012 |
|
|
Cut and Cap Storm Sewer |
Change Order #7 |
July 2012 |
|
|
Delete Sheet Metal From South Roof
Assembly |
Change Order #7 |
May 2012 |
|
|
Delete Steam Relief Assembly |
Pending Pricing |
June 2012 |
|
|
Replace SDR Pipe with Ductile Iron
@ Tunnel |
APP CHANGE ORDER 6 |
June 2012 |
|
|
Elevator Cab Heater |
Change Order #6 |
June 2012 |
|
|
Concrete Sill @ Curtain Wall - |
Change Order #6 |
May 2012 |
|
|
Taylor Hall East Addition
Foundation Waterproofing |
Change Order #6 |
May 2012 |
|
|
Concrete Well @ Louver L6 |
Change Order #6 |
May 2012 |
|
|
Site Fencing |
Pending Pricing |
June 2012 |
|
|
Stair Landings & Treads |
Pending MSU Approval |
July 2012 |
|
|
Ceramic Tile @ Lewis Restroom Rm 129 |
Change Order #6 |
June 2012 |
|
|
Chiller Eddy Testing - |
Change Order #6 |
May 2012 |
|
|
INFill Elevator Shaft East Elevation Lower Level |
Change Order #6 |
May 2012 |
|
|
Revised Landscaping Drawing |
Allowance-Bid |
May 2012 |
|
|
Delete VCT in Autoclave Rm 007 |
Change Order #6 |
April 2012 |
|
|
Remove & Replace Duct Smoke
Detectors – Keyed Test Switch |
Change Order #6 |
May 2012 |
|
|
Revise Casework A-30 & B-30
Types Add Epoxy Resin Tops |
Change Order #4 |
April 2012 |
|
|
Revise Emergency Shower Head
Location |
Pending Pricing |
April 2012 |
|
|
Delete Wall Assembly & Door
102C |
Change Order #6 |
April 2012 |
|
Alternate Road Access During
Sanitary Sewer Work |
Change Order #6 |
May 2012 |
||
|
Room 208 Electrical Power revisions |
Change Order #4 |
April 2012 |
|
|
Elevator Revisions – Maintenance
Req. MSU |
Change Order #6 |
May 2012 |
|
|
Casework-- Architectural Interior |
Pending Pricing |
April 2012 |
|
Room 212 Additions - Markerboard Video Monitor |
Change Order #4 |
April 2012 |
||
|
Video Monitors @ Collision Areas-
Pipe Chase wall assembly |
Change Order #4 |
April 2012 |
|
Basement Lighting Revisions |
Change Order #4 |
April 2012 |
||
Lewis Skybridge
Door security Revisions |
Pending Pricing |
May 2012 |
||
|
Vending Machines Power & Data |
Change Order #3 |
March 2012 |
|
Entry Grates @ West Entry & At ARC Entry |
Change Order #6 |
May 2012 |
||
|
Revision to Building Signage |
NO COST |
|
|
Delete VAC fittings/Piping |
Change Order #4 |
February 2012 |
||
|
Revised Autoclave Options |
Change Order #4 |
April 2012 |
|
Exposed GF CMU @ Basement Corridor |
Change Order #3 |
March 2012 |
||
|
Building Directories |
Change Order #4 |
May 2012 |
|
Unscheduled Booster Coils &
ERV Controls |
Change Order #3 |
March 2012 |
||
|
Revise Cooley – Lewis South Entry |
Change Order #7 |
August 2012 |
|
|
Revised Storm Drainage @ Lewis
Hall Retaining Wall Area |
Change Order #3 |
January 2012 |
|
High Impact DENS ARMOR PLUS |
Change Order #3 |
March 2012 |
||
|
Provisional Tees/Valves - Biobased Spray foam |
Change Order #3 |
January 2012 |
|
a |
Roof Plenum Drain Revisions |
Change Order #3 |
January 2012 |
|
|
Door Security/Revisions |
Change Order #3 |
May 2012 |
|
Lav Faucet Revision |
Change Order #3 |
May 2012 |
||
|
Basement Slab removal/replacement |
Change Order #2 |
December 2012 |
|
AHU Filter revisions |
Change Order #2 |
May 2012 |
||
|
RO Flush system (additional tees) |
Change Order #3 |
February 2012 |
|
Cooley Gas Meter-Utility reading
system |
Change Order #3 |
May 2012 |
||
|
|
|
|
|
r |
NW Building Heat |
Change Order #4 |
February 2012 |
|
ARC Corridor 125 Heat |
Change Order#4 |
April 2012 |
||
C |
ARC Corridor Lighting |
Change Order #4 |
April 2012 |
|
|
Dust Containment @ Autoclave ceiling
(ARC) |
Change Order #2 |
October 2011 |
|
|
Seismic Brick Issues - Spira Lok |
OPEN |
May 2012 |
|
B |
Parapet Revisions |
Change Order #3 |
December 2011 |
|
Natural Gas Service to Lewis |
Change Order #2 |
October 2011 |
||
|
Delete Liebert
Unit Room 208 |
Change Order #2 |
October 2011 |
|
Lewis
Cooley Flat Roof Connector System |
10-0023 Allowance Item |
Pending – Start May
2012 |
||
a |
Revise Roof Drain piping |
Change Order #3 |
March 2012 |
|
|
|
|
|
|
|
|
|
|
|